Permit Number: T22CM02179
Parcel: 12412063A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM02179
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2022 JPEELDA1 FIRE REVIEW Reqs Change Plans shall show the following:
Does the building have fire sprinklers
Does the building have a fire alarm
Occupancy type and Occupant Load
Egress plan
Defined Scope of Work

If you have any fire questions please contact me:

Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
04/07/2022 PCAMARE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
04/07/2022 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM02179
Building Plan Review
1540 E BROADWAY BL Zoning C-2

TRANSMITTAL DATE: April 7, ?2022


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1.COMMENT: As there are proposed changes to the site a Development Package meeting the requirements of the checklist for Minor Changes to Commercial/Industrial Site shall be submitted and approved prior to approval of this building permit. The checklist can be found at:
https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf. The DP is a separate submittal from this building permit and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using the Submission Type “Site Review”. This DP shall clearly show where the new drive thru will be placed on site.

2.COMMENT: Additional comments may be forthcoming.

If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
04/12/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0; Project Data: Please include data for the Occupancy Classification, Construction Type, Sprinklers, and Building Square Footage on this sheet.
2. Sheet A2.1; Elevation 2: Why is the Existing Front Elevation indicated here since there is no change being made on this wall? Please add the South Wall Elevation on this sheet to indicate the new drive-through window and dimensions.
3. Sheet S1.0; Section 2: Note 1 indicates "Grout cells at expansion bolts if required". Please indicate to grout the cells at the expansion bolt locations.
4. General: Please provide written responses to all review comments.
05/26/2022 SSHIELD1 ENGINEERING REVIEW Reqs Change See Zoning comments

Final Status

Task End Date Reviewer's Name Type of Review Description
05/26/2022 VVERA1 OUT TO CUSTOMER Completed