Permit Number: T22CM02081
Parcel: 121113800

Address:
5003 E ADAMS ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM02081
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/02/2022 SAMUEL ROGERS ZONING REVIEW Reqs Change FROM: Samuel Rogers
PDSD Zoning Review Section

PROJECT: T22CM02081
Addition
5003 E ADAMS ST Zoning R-2

TRANSMITTAL DATE: 5/02/2022


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


2.COMMENT: The proposed addition increases the size of the accessory structure to 742 Sqft, which is greater than 50% of the principle structure. Per UDC section 6.6.3.E "The total gross floor area (gfa) of all accessory structures shall not exceed 50% of the gfa of the principal structure ."
Porches and attached garages do not count towards the principal structure's GFA, so if any are present you may be able to remove them from your principal structure GFA. If you have any porches or attached garages identify their size in the lot coverage table.
If there are not any porches or attached garages you must either reduce the size of the proposed addition, or pursue a Board of Adjustments Variance: https://www.tucsonaz.gov/files/pdsd/codes/Zoning_Administration_Application_BA_fillable.pdf Contact Mark Castro for more information at mark.castro@tucsonaz.gov or 837-4979

4.COMMENT: The DDO T22SA00205 must be approved prior to the approval of this permit.

If you have any questions about this transmittal, Contact Samuel Rogers at (520) 837-6932 or by email Samuel.Rogers@tucsonaz.gov
05/04/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Add an exterior light at the exterior door, E3903.3.

Show the function of the existing room between the garage and addition. It may not be a bedroom because a garage door may not open into a bedroom, R302.5.1.