Permit Number: T22CM02053
Parcel: 11204211A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM02053
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/29/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A2; Egress Plan: The plan indicates various exit access travel paths (blue arrows), but nowhere is the actual exit access travel distance indicated for the various paths, and nowhere is there any indication of the allowable exit access travel distance listed (per the IBC Table 1017.2). Please provide.
2. Sheet A2 (Egress Plan); Sheet A3 (Floor Plan): A note under the Egress Plan indicates "24 seats 5% accessible 2 accessible seats required". Neither the Egress Plan or the Floor Plan indicate the 24 total seats or the 2 accessible seats. Please provide, and indicate the top of the tables are 34" above finish floor at the accessible seating.
3. Sheet A3; Interior Partition Wall Detail 1: Note 7 indicates "steel stud wall", but provides no information on the stud size, gauge, or spacing. A note at the bottom of this detail indicates to "see partition types", but that information was not located. PLease provide.
4. General: Please provide written responses to all review comments.
03/30/2022 WBERGER1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Wyatt Berger
Planner

PROJECT: T22CM02053
2510 E Fort Lowell Rd
Interior remodel (1st Review)

TRANSMITTAL DATE: March 30, 2022

This site is in the C-1 zone (UDC 4.7.20).

1. As new fencing and a new rolling gate are being proposed on this commercial site, a Development Package (DP) that meets the minimum requirements of the Checklist for Minor Changes to Commercial/Industrial sites must be submitted and approved. This checklist can be found at: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf.

If you have any questions about this transmittal, please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov.
03/30/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/03/2022 JVINCEN1 FIRE REVIEW Reqs Change See building comments.

john.vincent@tucsonaz.gov
520349-5581
04/12/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/12/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/12/2022 ROBERT SHERRY WATER REVIEW Completed
04/13/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/28/2022 IMONSHI1 ENGINEERING REVIEW Passed