Permit Number: T22CM02051
Parcel: 119223450

Address:
1974 W SAXONY RD

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM02051
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2022 IMONSHI1 ENGINEERING REVIEW Passed
03/23/2022 IMONSHI1 NPPO REVIEW Passed
03/29/2022 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T22CM02051
1974 W Saxony Rd – R-1
Porch Addition (1st Review)

TRANSMITTAL March 29, 2022

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9.

1. Per UDC Article 6.4.5.C.1.a the required front street perimeter yard setback is 20’-0”. Proposed setback shows 18’-0”. Per UDC Article 6.4.5.B.2 for porch type structures the setback is measured from the post support the roof structure as long as the roof overhang does not exceed 2’-0”. Clearly show the post supporting the roof and provided a dimension from the post to the street property line. If the setback is less than 20’-0” a Design Development Option (DDO) must be submitted and approved to reduce the required setback,
DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov.

2. Based on current aerial photos there is an addition on the rear of the house that does not appear to have been permitted. Either provide approved permit documentation of include this area in this permit.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
04/13/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T22CM02051
PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.
GENERAL REQUIREMENTS:
The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.
Consolidate pages of construction plans into a single .PDF file as prescribed at the PDSD web site. https://www.tucsonaz.gov/pdsd/online-permits
Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits
GENERAL COMMENTS:
1. Items built without permit may require alteration or improvement for achieving code compliance with the 2018 IRC, R105. Complete construction plans are required for processing a building permit. The plans should show necessary structural changes for achieving building code compliance, 2018 IRC.

SITE PLAN:
1. Indicate the location of buildings and any utilities supporting or effecting the proposed structure. Include the electrical line.

FOUNDATION PLAN:
1. Dimension the footing length, width, and depth into undisturbed soil for each footing type and condition, R403.1. Show the minimum 12” reinforced footing depth below the undisturbed ground surface R403.1. Show rebar reinforcement with 3” clearance from earth, R403.1.3.5.3. Also, show column rebar size.

FRAMING PLAN:
1. Provide a complete roof framing plan with beams and rafters sized with appropriate load carrying capacity for each structure, R301.1.

ELECTRICAL PLANS:
1. Show the overhead service conductor with an 8-foot clearance above the roof, E3604.2.1 or relocate the service panel from under the roof. The service line change or a new panel location must be coordinated with TEP for approval.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
520 837-4912