Permit Number: T22CM02041
Parcel: 12101103E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM02041
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/29/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/31/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Verify that the new exam room has a ducted return to the HVAC system and is not using the corridor as a return duct. Reference: Section 601.2, IMC 2018.
03/31/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
03/31/2022 ROBERT SHERRY WATER REVIEW Completed
04/03/2022 JVINCEN1 FIRE REVIEW Approved
04/05/2022 STEVE SHIELDS ZONING REVIEW Approved
04/05/2022 SSHIELD1 ENGINEERING REVIEW Passed
04/05/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/14/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved