03/21/2022 ARUIZ1 OIP REVIEW Reqs Change It appears 1/2 inch pipe to the two water heaters is undersized and would require at least 3/4 inch pipe.
A typical range has a BTU of 65K, 15K is not a reasonable number for a 4 plus burner. 1" pipe size would be required to the range.