Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM01968
Parcel: 12419026C

Address:
1881 E 18TH ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM01968
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/25/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM01968

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. The occupant load calculated for the business area is incorrect. The occupant load factor for business is 150. Provide a correct occupant load in accordance with Table 1004.5.
2. Provide a narrative that describes the business practices of the tenant and the typical items in storage to ensure compliance with storage requirements of the IBC and IFC.
3. Provide raised character and braille exit signs in accordance with Section 1013.4


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Denied
1. The plans do not reflect the plan location and single line illustration of the electrical equipment. Provide the location of the panel box and a single line diagram confirming the conductor size and overcurrent protection of the transformer or main panel providing power to and protecting this system.


PLUMBING REVIEW COMMENTS:
Denied
1. The construction plans shall include for each floor level a riser diagram of the supply water, and gas work. The construction plans shall indicate the direction of flow, all pipe sizes, grade of horizontal piping, loading, and location of fixtures and appliances. Provide a rise diagram for each plumbing system, including gas piping if part of the project.
2. To ensure compliance of the gas line design the Gas type, Inlet pressure, Pressure Drop, and Specific Gravity, also provide a gas load summary, size of all piping (this information is lacking at the piping feeding the fixtures and the amount of BTUs coming in at meter. Please provide more details for the sizing of the gas lines.
3. The location of water heater must be provided on the floor plan. If the water heater is suspended above the floor, provide a detail for the structural support, pressure relief valve discharge, cold water and hot water piping along with the shutoff valves, expansion tank, etc. Revise plans to reflect this information.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/31/2022 SSHIELD1 ENGINEERING REVIEW Passed
03/31/2022 STEVE SHIELDS ZONING REVIEW Approved
03/31/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/03/2022 JVINCEN1 FIRE REVIEW Reqs Change See building comments.

john.vincent@tucsonaz.gov
5203495581
04/18/2022 ROBERT SHERRY WATER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
04/18/2022 VVERA1 OUT TO CUSTOMER Completed