Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM01955
Parcel: 117150040

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM01955
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; Code Review: Per the IBC Section 1004.9, every space that is an assembly occupancy shall have the occupant load of that space posted. Please indicate this in the Code Review.
2. Sheet A1 (Code Review); Sheet A5 (Floor Plan): The Occupant Load calculation in the Code Review considers only the seating area (1200 SF), the service area (663 SF), and the restrooms (2 occupants). The Floor Plan indicates two areas in the basement as "non-usable-unfinished". Will these areas be used for storage? If so, the Occupant Load should include those areas.
3. Sheet A5; Floor Plan: The interior partition sections indicate 2/A4 on this plan. Please revise.
4. General: Please provide written responses to all review comments.
03/24/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Clarify the location of the condensing units. Show how they are accessible for maintenance. If necessary, provide protection for the refrigerant access ports. Reference: Sections 306.5 and 1102.3, IMC 2018.
03/24/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the partial water isometric, B/P2, to show the hot water recirculation loop continuing from one lavatory to the next lavatory (see also keynotes 4 and 5 on sheet P1). Reference: Section C404.5, IECC 2018.
2. Specify that all proposed plumbing fixtures (e.g. "owner specified") shall be listed by a third-party certification agency as complying with the relevant standards. Reference: Section 303.4, IPC 2018.
3. Clarify the orientation of the waste fittings south of the two restrooms, near keynote 1 on sheet P1. Reference: Section 706.3, IPC 2018.
03/24/2022 ROBERT SHERRY WATER REVIEW Completed
03/31/2022 STEVE SHIELDS ZONING REVIEW Approved
03/31/2022 SSHIELD1 ENGINEERING REVIEW Passed
03/31/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/13/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/11/2022 JPEELDA1 FIRE REVIEW Reqs Change 1. Sheet A1; Code Review: Per the IBC Section 1004.9, every space that is an assembly occupancy shall have the occupant load of that space posted. Please indicate this in the Code Review.
2. Sheet A1 (Code Review); Sheet A5 (Floor Plan): The Occupant Load calculation in the Code Review considers only the seating area (1200 SF), the service area (663 SF), and the restrooms (2 occupants). The Floor Plan indicates two areas in the basement as "non-usable-unfinished". Will these areas be used for storage? If so, the Occupant Load should include those areas. If not storage please indicate the rooms purpose and occupant load.

Questions:
Jennifer Peel-Davis
Fire Plans Examiner
520-837-7033
Jennifer.Peel-Davis@Tucsonaz.gov