Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM01952
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/26/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/28/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Completed | |
| 05/17/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Your house is 3,851 sq ft under the roof and requires a fire flow of 1,750 GPM for 2 hours. Unfortunately, you only have 1 hydrant designed at 1,000 GPM for 2 hours within 600 feet of your entire house. You shall install fire sprinklers. Plans shall have a note: Fire sprinklers shall be installed and a permit obtained from TFD. You will also need to speak to Tucson Water about upsizing your meter to accommodate the fire sprinkler system. Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 Fire Plans Examiner |