Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM01944
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/23/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/23/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/23/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 03/24/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the glass designation on sheet A82 to show a maximum SHGC of 0.25 and a maximum U-factor of 0.50. Reference: Section C402.4, IECC 2018. 2. The minimum required ventilation for a fitness is different from a break room. Provide ventilation calculations for the fitness room and show how the ventilation will be provided. The ventilation rate is to be based on Table 403.3.1.1, IMC 2018, or an approved engineering analysis of the specific occupancy type. Reference: Section 403.3.1.1, IMC 2018. |
| 03/30/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 03/30/2022 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 03/30/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/03/2022 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 04/11/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |