Permit Number: T22CM01944
Parcel: 13409010A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM01944
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/23/2022 ROBERT SHERRY WATER REVIEW Completed
03/23/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/24/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the glass designation on sheet A82 to show a maximum SHGC of 0.25 and a maximum U-factor of 0.50. Reference: Section C402.4, IECC 2018.
2. The minimum required ventilation for a fitness is different from a break room. Provide ventilation calculations for the fitness room and show how the ventilation will be provided. The ventilation rate is to be based on Table 403.3.1.1, IMC 2018, or an approved engineering analysis of the specific occupancy type. Reference: Section 403.3.1.1, IMC 2018.
03/30/2022 STEVE SHIELDS ZONING REVIEW Approved
03/30/2022 SSHIELD1 ENGINEERING REVIEW Passed
03/30/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/03/2022 JVINCEN1 FIRE REVIEW Approved
04/11/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved