Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM01937
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/03/2022 | ARUIZ1 | OIP | REVIEW | Reqs Change | TRANSMITTAL DATE: May 3, 2022 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed. COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments COMMENT: Label the location of the Rapid Shutdown device, NEC 690.56(C). Devices or components may not negatively affect the equipment integrity or listing, NEC 110.3. Show specs for the panel listing allowing the proposed installation of lugs. COMMENT: Residential will review the application on the next submittal If you have any questions about this transmittal, Contact Angie.Ruiz@Tucsonaz.gov any time during the week by email RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/04/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |