| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/03/2022 | PCAMARE1 | OIP | REVIEW | Reqs Change | Transmittal Template FROM: Paul Camarena PDSD Residential Review Section PROJECT:T22CM01887 Roof top Solar Panels (1st Review) 1641 W CIRCLE A DR TRANSMITTAL DATE: May 3, 2022 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed. ? COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments. COMMENT: COMMENT: The Plan Set shows a line-side tap, Line taps require compliance with NEC 230.46. Update the plans showing a tap enclosure with sufficient space for the tap device, or show a meter socket extension with tap terminals (approved Milbank tapping device) ? COMMENT: Residential will review the application on the next submittal If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.Camarena@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |