Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T22CM01873
Parcel: 140150590

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM01873
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2022 IMONSHI1 ZONING REVIEW Approved
03/22/2022 IMONSHI1 ENGINEERING REVIEW Passed
03/22/2022 IMONSHI1 NPPO REVIEW Passed
04/13/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM01873

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. 2018 IRC Section R310. Revise drawings with emergency escape and rescue opening net clear dimension of window when fully open for sleeping room (bedroom).
2. 2018 IRC Section 314.2, R314.3 and R314.4. Revise electrical drawing with smoke alarms in bedroom and outside of bedroom areas and to be interconnected in such a manner that the actuation of one alarm will activate all of the alarms in the individual dwelling unit.
3. 2018 IRC Section R806. Revise drawings with roof cross ventilation openings including minimum of 1-inch space between the insulation and roof sheathing or provide unvented enclosed rafter framing with air-permeable insulation (R806.5.2 climate zone 2).
4. 2018 IRC Section R903, R904 and 905. Revise drawings with roof weather protection and roof covering.
5. 2018 IRC (Prescriptive) Table N1102.1.2 (R402.1.2). Revise rafter size for ceiling insulation of R-38 with 12 inches of space in depth required for fiberglass insulation between 2 x 12 rafters or provide unvented enclosed rafter framing with air-permeable insulation totaling R-38 (R806.5.2 climate zone 2).


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Denied
1. 2018 IRC Section E3401.2. Electrical systems, equipment or components not specifically covered in IRC chapters 34 through 43 shall comply with the provisions of NFPA 70.
2. 2018 IRC Section E3902.16 and E3902.17. Revise electrical drawing with arc-fault circuit-interrupter protection for branch circuits 120-volt, single-phase, 15- and 20-ampere outlets installed in kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreations rooms, closets, hallways, laundry areas and similar rooms or areas.
3. 2018 IRC Section E4002.14. Tamper resistant receptacles are required in most locations.


PLUMBING REVIEW COMMENTS:
Approved

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov