06/08/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Provide a complete set of construction plans showing 2018 IRC compliance.

1. Show a complete cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12” x 12” continuous #4 rebar reinforced footing, R403.1. Show exterior wood siding, sheathing and wall framing anchored with ½" x 10" bolts and with pressure treated sill. Show exterior wood siding, sheathing and wall framing with a 6" clearance above the ground, R317.1 item 5.

2. Interior alterations require the installation of smoke alarms at existing bedrooms, R314.2.2. Provide notation if the smoke alarms are existing or proposed.

3. Show Bathroom lighting, fan and a receptacle with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6.

4. Show Bedroom receptacles with arc-fault propection.

5. Show Bedroom lighting.

6. Show the Bedroom heating and cooling device.
06/20/2022 PAUL CAMARENA ZONING REVIEW Approved