Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM01866
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/08/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Provide a complete set of construction plans showing 2018 IRC compliance. 1. Show a complete cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12” x 12” continuous #4 rebar reinforced footing, R403.1. Show exterior wood siding, sheathing and wall framing anchored with ½" x 10" bolts and with pressure treated sill. Show exterior wood siding, sheathing and wall framing with a 6" clearance above the ground, R317.1 item 5. 2. Interior alterations require the installation of smoke alarms at existing bedrooms, R314.2.2. Provide notation if the smoke alarms are existing or proposed. 3. Show Bathroom lighting, fan and a receptacle with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6. 4. Show Bedroom receptacles with arc-fault propection. 5. Show Bedroom lighting. 6. Show the Bedroom heating and cooling device. |
| 06/20/2022 | PAUL CAMARENA | ZONING | REVIEW | Approved |