Permit Number: T22CM01860
Parcel: 132131260

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM01860
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2022 VFLORES1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change PLEASE CONTACT PC ADDRESSING UNIT NUMBER NEEDS TO BE ASSIGNED PRIOR TO ISSUANCE PH# 520-724-9512 EMAIL: ADDRESSING@PIMA.GOV
03/24/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM01860

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. Sheet A102: The accessible routes through the space seem to below the minimum required width. Please indicate clearly the accessible routes throughout the space.
2. Sheet A102: The equipment in the service counter area and kitchen seem to impeded beyond the maximum allowances. Provide a clear circulation path in accordance with Section 1003.3.3 and 1003.6.
3. Sheet A102: Provide a dimensioned equipment floor plan to ensure compliance with required minimum exit width capacities for seating. Provide evidence of the compliance with Section 1029.13.1.
4. Sheet A103: Additional exit signs are requested adjacent to the open kitchen and dining area that indicate the direction the exits in accordance with Section 1013.1.
5. Raised character and braille exits sings are required at each exit discharge. Provide exit signage in accordance with Section 1013.4.


MECHANICAL REVIEW COMMENTS:
Denied
1. Sheet M101: Provide evidence of compliance of exhaust outlet separation from mechanical air intakes in accordance with IMC Section 501.3.1.


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
1. Floor drain #2 is required to be a greases interceptor and drain to the grease line in accordance with Section 1003.3.1.
2. Roof equipment condensate cannot discharge to the grease system. Provide a correct drainage solution for this occurrence in accordance with Section 1003.2.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/29/2022 SSHIELD1 ENGINEERING REVIEW Passed
03/29/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM01860
3460 S Kino Pkwy – PAD-15
New Food Service (1st Review)

TRANSMITTAL: March 29, 2022
This site is located in PAD-15 Food Service is an allowed use in the PAD.

1. Zoning has reviewed the building plans for compliance with DP21-0213 and the following comments need to be addressed. Until DP21-0213 is approved Zoning cannot approve the building plan.

2. The covered patio area does not match what is shown on DP21-0213. Either the DP or building plans will need to be revised to match.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
03/29/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
04/03/2022 JVINCEN1 FIRE REVIEW Approved
04/07/2022 JGARCIA1 WATER REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
04/07/2022 NGARCIA3 OUT TO CUSTOMER Completed