Review Date Reviewer's Name Type of Review Description Status Comments
03/29/2022 SSHIELD1 ENGINEERING REVIEW Passed
03/29/2022 STEVE SHIELDS ZONING REVIEW Approved
03/29/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/30/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM01855

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide Structural Calculations for New 3.5x9 GLB Roof Joists supporting New Mechanical Units. The Calculations submitted only considered roof Dead and Live Loads. Verify if the Joists size is adequate where the RTU’s are present.
2. Provide Structural Calculations for New 8.75x16.5 GLB Roof Girder supporting New Mechanical Units. The Calculations submitted only considered roof Dead and Live Loads. Verify if the Girder size is adequate where the RTU’s are present.
3. All Calculations shall be sealed and signed by Professional Engineer registered with State of Arizona per Section 107.1 of International Building Code 2018.
Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.


BUILDING REVIEW COMMENTS:
Denied
1. Cover Sheet: The allowable sq ft. listed is incorrect. Provide a corrected allowable sq ft in accordance with Table 506.2.
2. Sheet CC1.0:Provide a total updated calculated occupant load that includes the areas that are not in scope.
3. Sheet CC1.0:The occupant load for the fixed seating is incorrect. Provide a corrected occupant load along with the calculations in accordance with Section 1004.6.
4. Sheet CC1.0:The occupant load for the juice bar is incorrect. This occupant load factor does not appear on Table 1004.5. The juice bar would be part of the open area. Provide a corrected occupant load.
5. Sheet CC1.0:The exit plan does not indicate the width of exit access components or travel distances. Provide all necessary dimensions and travel distances.
6. Sheet CC1.0: The construction type listed is not a construction type that is recognized by the IBC. Provide a corrected construction type in accordance with Chapter 6.
7. Sheet CC1.0: Show all exit lighting on the exit plan in accordance with Section 1013.
8. Show all existing floor plans.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E4.0: 2 Comments:
Panel VIP CB 29, 31 for CU-3 should have a 30-amp CB or smaller to match HVAC Equipment schedule on sheet E2.0. Otherwise upsize fused disconnect and wire on sheet E2.0.
General Note #3 is unreadable.


PLUMBING REVIEW COMMENTS:
Denied
First Review:
1). Add Plumbing plans with illustrations, information, specifications, & fixture schedule for the relocated & added restroom fixtures shown on plan pages D1.0 & A1.0. and for all the plumbing related work involved with the added Juice Bars. -IPC A106.3.1




If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/30/2022 JPEELDA1 FIRE REVIEW Reqs Change Denied
1. Cover Sheet: The allowable sq ft. listed is incorrect. Provide a corrected allowable sq ft in accordance with Table 506.2.
2. Sheet CC1.0:Provide a total updated calculated occupant load that includes the areas that are not in scope.
3. Sheet CC1.0:The occupant load for the fixed seating is incorrect. Provide a corrected occupant load along with the calculations in accordance with Section 1004.6.
4. Sheet CC1.0:The occupant load for the juice bar is incorrect. This occupant load factor does not appear on Table 1004.5. The juice bar would be part of the open area. Provide a corrected occupant load.
5. Sheet CC1.0:The exit plan does not indicate the width of exit access components or travel distances. Provide all necessary dimensions and travel distances.
6. Sheet CC1.0: The construction type listed is not a construction type that is recognized by the IBC. Provide a corrected construction type in accordance with Chapter 6.
7. Sheet CC1.0: Show all exit lighting on the exit plan in accordance with Section 1013.
8. Show all existing floor plans.
04/13/2022 ROBERT SHERRY WATER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
04/14/2022 VVERA1 OUT TO CUSTOMER Completed