Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM01803
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2022 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM01803
Carport (1st Review)
9225 E 29TH ST Zoning R-1

TRANSMITTAL DATE: ?March ?22, ?2022


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

COMMENTS: Provide a Residential Plot Plan that meets the requirements found at:
https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf. This shall include: Please show all new and existing structures on site.
a. Actual setback dimension.
c. All Utility lines
d. Property line distances
I have provided a link with a plot plan
https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Grid.pdf

If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
03/23/2022 IMONSHI1 ENGINEERING REVIEW Passed
03/23/2022 IMONSHI1 NPPO REVIEW Passed
04/05/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change 1. The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

2. Consolidate pages of construction plans into a single .PDF file as prescribed at the PDSD web site.

3. Provide an accurate site plan showing the location of alterations.

4. Show the door from a garage to dwelling with a 20-minute fire rating (or 1-3/8" solid core) with self-closing and self-latching provision, R302.5.1.

5. Show any roof framing alterations and beam sizes. A pipe column supporting roof loads requires a reinforced foundation.

6. Show the minimum 12" footing depth below the undisturbed ground surface with 12" minimum width for wood framed walls with minimum of one #4 rebar in the proposed continuous footing, R403.1.

7. Show the minimum hardboard sheathing thickness of 7/16", Table R703.4e.

8. Garage Receptacle: a 20 AMP receptacle outlet is required at each vehicle bay not more than 5.5 feet above the floor, E3901.9.