Permit Number: T22CM01801
Parcel: Unknown

Address:
1557 W PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM01801
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the size of the existing water service to the building. The plumbing floor plan shows 1-1/4" but the water isometric shows 2". Reference: Section 107.2.1, IBC 2018.
2. Verify that the distance from the hot water source to the hot water termination for the new public lavatories complies with the requirements of Section C404.5, IECC 2018.
03/17/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/17/2022 ROBERT SHERRY WATER REVIEW Reqs Change Tucson Water limits 5/8" water meters to maximum demand of 20 GPM. Provide a letter from Tucson Water confirming that the use of a 5/8" water meter will be allowed for this project with a demand of 23 GPM).
03/21/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/22/2022 JPEELDA1 FIRE REVIEW Approved
03/29/2022 STEVE SHIELDS ZONING REVIEW Passed
03/29/2022 SSHIELD1 ENGINEERING REVIEW Passed
03/29/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/07/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved