Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM01795
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/23/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/06/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide written response. 1. The voltage rating of the new panel 'A' was revised to 277/480 volts. The electrical plan shows the office receptacles and all lighting branch circuits being fed from this panel. Are all these devices rated for 277 volts? Please clarify. Ref 2018 IBC, 2018 IECC, 2017 NEC. |