Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM01795
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/17/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
03/17/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
03/17/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
03/21/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A0; Floor Plan: Please indicate on this plan the gauge of the new partition wall studs. 2. Sheet A0: Please provide a detail on this drawing indicating the bracing at the top of the new partition walls required to resist a horizontal load of 5 PSF per the IBC Section 1607.15. Include the bracing size, spacing, and details of the connection of the bracing to the existing structure and to the new partition walls. 3. General: Please provide written responses to all review comments. |
03/22/2022 | JPEELDA1 | FIRE | REVIEW | Approved | |
03/25/2022 | WBERGER1 | ZONING | REVIEW | Approved | |
03/25/2022 | WBERGER1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/06/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. The electrical one-line diagram that feeds the new Panel ‘A’ shows the AC System rated at 277/480 volts 3 phase. The panel schedule for Panel ‘A’ shows a 120/208 volt rated panel. Please clarify. 2. Provide lighting controls (Occupancy Sensers) as required in the office area per section C405.2.1.3, 2018 IECC. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |
05/13/2022 | SBLOOD1 | ENGINEERING | REVIEW | Passed |