Permit Number: T22CM01795
Parcel: 12404100C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM01795
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/17/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/17/2022 ROBERT SHERRY WATER REVIEW Completed
03/21/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A0; Floor Plan: Please indicate on this plan the gauge of the new partition wall studs.
2. Sheet A0: Please provide a detail on this drawing indicating the bracing at the top of the new partition walls required to resist a horizontal load of 5 PSF per the IBC Section 1607.15. Include the bracing size, spacing, and details of the connection of the bracing to the existing structure and to the new partition walls.
3. General: Please provide written responses to all review comments.
03/22/2022 JPEELDA1 FIRE REVIEW Approved
03/25/2022 WBERGER1 ZONING REVIEW Approved
03/25/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/06/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. The electrical one-line diagram that feeds the new Panel ‘A’ shows the AC System rated at 277/480 volts 3 phase. The panel schedule for Panel ‘A’ shows a 120/208 volt rated panel. Please clarify.

2. Provide lighting controls (Occupancy Sensers) as required in the office area per section C405.2.1.3, 2018 IECC.

Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
05/13/2022 SBLOOD1 ENGINEERING REVIEW Passed