Permit Number: T22CM01791
Parcel: Unknown

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM01791
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2022 PAUL CAMARENA ZONING REVIEW Approved
03/22/2022 PCAMARE1 NPPO REVIEW Passed
04/08/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM01791

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Denied
1. 2018 IRC Section R106.1.1. Revise sheet A108 by removing all references to 2012 International Residential Code and indicate 2018 International Residential Code with City of Tucson Amendments.
2. 2018 IRC Section M1411.3. Revise drawings with condensate disposal from mechanical equipment.
3. 2018 IRC Section M1501.1 and M1504.3. Revise plans with every mechanical exhaust system discharge to the outdoors and not into an attic, soffit, ridge vent or crawl space.
4. 2018 IRC Section M1502.3. Revise plans with clothes dryer exhaust termination on the outside of the building and not less than 3 feet from any openings.
5. 2018 IRC Section M1502.4.1 and M1502.4.2. Revise plans with clothes dryer exhaust duct details including type of metal, thickness and joints cannot have screws or fasteners that protrude more than 1/8 inch into the inside of duct.


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
1. 2018 IRC Section P2712 and P3005.1.4. Revise drawings with minimum drain size of not less than 3 inches in diameter for water closet (toilet) drain.
2. 2018 IRC Section P2903.9.1. Revise drawings with an accessible main full-open type shutoff valve near the entrance of the water service.
3. 2018 IRC Section P3105. Revise plumbing drawing with a vent for each fixture trap.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
05/02/2022 SBLOOD1 ENGINEERING REVIEW Passed