Permit Number: T22CM01785
Parcel: 133090310

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM01785
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2022 PAUL CAMARENA ZONING REVIEW Approved
03/22/2022 PCAMARE1 ENGINEERING REVIEW Passed
03/22/2022 PCAMARE1 NPPO REVIEW Passed
04/05/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change 1. The enclosed carport is shown as a garage with a vehicle door; therefore lable the space as a garage rather than game room or replace the vehicle door with an insulated wall.

2. Show all doors opening into the dwelling with a 20-minute fire rating (or 1-3/8" solid core) with self-closing and self-latching provision, R302.5.1.

3. Show exterior walls with a minimum ½" diameter anchor bolt or expansion bolt, R602.10.8 & R403.1.6. Ram set pins are only appropriate for interior patrician walls. Update note #2.

4. Show exterior wall framing with a 6" clearance above the ground (R317.1 item 5) and with pressure treated sill plates, R602.10.8 & R403.1.6. This may require a concrete stem when the floor is less than 6" above grade or 2" above exterior concrete surfaces. Update th Footing Detail.

5. Garage Branch Circuit: a separate (dedicated) GFCI 20-amp branch circuit required for receptacles in an attached garage and detached garages with service, E3703.5.