Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM01785
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/22/2022 | PAUL CAMARENA | ZONING | REVIEW | Approved | |
| 03/22/2022 | PCAMARE1 | ENGINEERING | REVIEW | Passed | |
| 03/22/2022 | PCAMARE1 | NPPO | REVIEW | Passed | |
| 04/05/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | 1. The enclosed carport is shown as a garage with a vehicle door; therefore lable the space as a garage rather than game room or replace the vehicle door with an insulated wall. 2. Show all doors opening into the dwelling with a 20-minute fire rating (or 1-3/8" solid core) with self-closing and self-latching provision, R302.5.1. 3. Show exterior walls with a minimum ½" diameter anchor bolt or expansion bolt, R602.10.8 & R403.1.6. Ram set pins are only appropriate for interior patrician walls. Update note #2. 4. Show exterior wall framing with a 6" clearance above the ground (R317.1 item 5) and with pressure treated sill plates, R602.10.8 & R403.1.6. This may require a concrete stem when the floor is less than 6" above grade or 2" above exterior concrete surfaces. Update th Footing Detail. 5. Garage Branch Circuit: a separate (dedicated) GFCI 20-amp branch circuit required for receptacles in an attached garage and detached garages with service, E3703.5. |