Permit Number: T22CM01739
Parcel: 133270390

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM01739
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2022 PCAMARE1 OIP REVIEW Reqs Change Transmittal Template


FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T22CM01739
Roof top Solar Panels (1st Review)
8041 E HAWTHORNE ST

TRANSMITTAL DATE: April 27, 2022



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


? COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments.


COMMENT: This plan set is not compliant with the Fire code. On roof #1 demonstrate compliance with 2018 International Fire Code 1204.2.1.1. If the slope of the building is greater than 2:12 then compliance must be shown on the plans. Show a 36” wide access pathway from the eave to the ridge on both sides of the building. Relocate the solar panels to provide a clear fire pathway on each roof plane per 2018 IFC 1204.2.1.1 and 1204.2.1.2.

? COMMENT: Residential will review the application on the next submittal




If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.Camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans

Final Status

Task End Date Reviewer's Name Type of Review Description
04/27/2022 VVERA1 OUT TO CUSTOMER Completed