Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM01692
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/05/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/05/2022 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 04/05/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The exhaust air flow rate exceeds the make-up air flow rate by 600 CFM. Show how adequate make-up air is to be provided to the room so that the room pressure remains essentially neutral. Reference: Sections 501.4 and 508.1.2, IMC 2018. 2. Verify that the exhaust termination will be located in accordance with the requirements of Section 506.3.13, IMC 2018. |
| 04/05/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/05/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |