Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/05/2022 JPEELDA1 FIRE REVIEW Approved
04/05/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The exhaust air flow rate exceeds the make-up air flow rate by 600 CFM. Show how adequate make-up air is to be provided to the room so that the room pressure remains essentially neutral. Reference: Sections 501.4 and 508.1.2, IMC 2018.
2. Verify that the exhaust termination will be located in accordance with the requirements of Section 506.3.13, IMC 2018.
04/05/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed