| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/09/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | FROM: Paul Camarena PDSD Zoning Review Section PROJECT: T22CM01667 Electrical 505 S COLUMBUS BL Zoning R-1 TRANSMITTAL DATE : May 9, 2022 COMMENTS: Please resubmit revised drawings with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. This comment was not addressed. COMMENT: Although there is a permit for the detached accessory structure. After researching PRO there are records for an expired permit T14CM02394, there are outstanding inspections. A"Finals only permit" will have to be obtained and the permit referenced above must be finalized. Prior to zoning approval If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov |
| 05/09/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Appliances and equipment on general purpose circuits may not exceed 50% of the branch circuit rating, E3702.5. Show a circuit for each radiant heating unit. Provide a feeder load calculation for the 50 AMP sub-panel as shown at Table E3704.2(1). |