Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM01658
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM01658
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet TS1: Please provide a plan on the drawings indicating the Exit Access Travel Distance. Verify on this sheet the actual distance meets the requirements of the IBC Table 1006.2.1 (100' maximum with one exit).
2. Sheet A1.0; Floor Plan: Keynote 11 does not indicate the gauge of the new wall studs. Please provide.
3. Sheet A1.0: Please provide a detail for the bracing of the new interior walls at the top. Indicate the brace member size, gauge, spacing, and connection to the existing structure and to the top of the wall.
4. General: Please provide written responses to all review comments.
03/16/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/16/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
03/16/2022 ROBERT SHERRY WATER REVIEW Completed
03/21/2022 JPEELDA1 FIRE REVIEW Reqs Change 1. Sheet TS1: Please provide a plan on the drawings indicating the Exit Access Travel Distance. Verify on this sheet the actual distance meets the requirements of the IFC Table 1006.2.1 (100' maximum with one exit).

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
03/25/2022 STEVE SHIELDS ZONING REVIEW Approved
03/25/2022 SSHIELD1 ENGINEERING REVIEW Passed
03/25/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
03/30/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved