Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM01632
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/07/2022 | GSLEIGH1 | PIMA COUNTY - ADDRESSING | PIMA COUNTY - ADDRESSING | Reqs Change | Duplex requires unit numbers. Please contact Pima County Development Services to update address information. |
| 03/08/2022 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 03/21/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T22CM01632 2019 & 2021 E 2nd St - R-2 Laundry Room Addition to both Units of a Duplex. (1st Review) TRANSMITTAL: March 21, 2022 This site is located in the R-2 zone (UDC 4.7.9). A duplex is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10. 1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf, to include but not limited to: a. Provide a lot coverage calculation on the plot plan. b. Show the location of all utilities on the plot plan. c. Provide the zoning for all adjacent parcels. d. Provide the legal description on the plot plan. e. Provide the property dimensions on the plot plan. f. The entire parcel should be shown on the plan. g. Provide a setback dimension to the north property line. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
| 03/23/2022 | IMONSHI1 | NPPO | REVIEW | Passed | |
| 03/30/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T22CM01632 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet Zoning and other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans. Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits SITE PLAN: 1. Show the location and size of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1. Identify the utility lines requiring upgrade or replacement. SECTIONS - DETAILS: 1. Show a complete cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12” reinforced footing depth below the undisturbed ground surface R403.1. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground, R317.1 item 5. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground, R317.1 item 5. This dimension is required in addition to the 4” weep screen clearance for a compliant foundation and floor height. Update the elevations and include the below grade foundation. PLUMBING PLANS: 1. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Provide a gas line isometric or table for showing the BTU demand and length of line to each gas appliance from the gas meter. OUTDOOR LIGHTING CODE 1. Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. If you have any questions, please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |