Permit Number: T22CM01598
Parcel: 11504602D

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM01598
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Ref; Plan sheet E3.0. The Electric Load Summary calls for an 800-amp Panel. The Panel schedule shows an 800 amp Panel ‘MSB’ . Why does the line diagram show a 600 amp Switchboard ‘MSB’ with a 600 amp main breaker?

2. Verify that the panels being refed by the new electrical service are rated for 22k and 42K AIC per the Fault Current Analysis.

Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements

Final Status

Task End Date Reviewer's Name Type of Review Description
03/30/2022 VVERA1 OUT TO CUSTOMER Completed