| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/30/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. Ref; Plan sheet E3.0. The Electric Load Summary calls for an 800-amp Panel. The Panel schedule shows an 800 amp Panel ‘MSB’ . Why does the line diagram show a 600 amp Switchboard ‘MSB’ with a 600 amp main breaker? 2. Verify that the panels being refed by the new electrical service are rated for 22k and 42K AIC per the Fault Current Analysis. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |