Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM01577
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/20/2022 | PCAMARE1 | OIP | REVIEW | Reqs Change | Transmittal Template FROM: Paul Camarena PDSD Residential Review Section PROJECT:T22CM01577 Roof top Solar Panels (1st Review) 5959 S ANTRIM LP TRANSMITTAL DATE: ?April ?20, ?2022 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed. ? COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments. COMMENT: Provide permit documentation for the existing PV system 22 modules. ? COMMENT: Residential will review the application on the next submittal If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.Camarena@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/20/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |