Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T22CM01576
Parcel: 305977230

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM01576
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2022 ARUIZ1 OIP REVIEW Reqs Change The 95 foot run to the BBQ and FT (120,000 BTU) is undersized at 3/4'. It would need to be at least 1' to comply.
For questions contact Angie.Ruiz@Tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
03/07/2022 NGARCIA3 OUT TO CUSTOMER Completed