Permit Number: T22CM01548
Parcel: 123072530

Address:
2116 E HELEN ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM01548
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed
04/15/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM01548
2116 E Helen St. - R-1
Attached Garage (2nd Review)

TRANSMITTAL: April 15, 2022

Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).


This site is located in the R-1 zone (UDC 5.10.3). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.



1. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). As a dimension was not provide to design grade Zoning added 6” to the provided 12’-4” dimension. Based on a wall height of 12’-10” the required perimeter yard setback from the proposed garage addition to the west property line is 8’-6”, proposed setback is 1’-0”. A Design Development Option (DDO) must be submitted and approved to reduce the required setback, DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov.

2. This comment was not addressed. Based on aerial photos there was a detached garage in the rear yard that has been demolished. This structure was over 50 year old and requires Historic review.
The Pima County Assessor’s effective construction date for your building or structure is 1943. The actual construction date may be earlier.
Buildings, portions of buildings or structures that are 50 years of age or older must be architecturally documented prior to demolition. Documentation will be reviewed and approved by the Historic Preservation Office before a permit is issued.
Demolition (Historic and Older Structures) Application and General Information may be downloaded (PDF) at https://www.tucsonaz.gov/pdsd/all-application-forms-submittal-requirements
Return completed documentation to PDSDHistoric@tucsonaz.gov. Applicant will be contacted within 5 working days if additional materials are required for review. Until the Historic review is completed and approved Zoning will not be able to approve attached garage permit.
If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.