Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM01507
Parcel: 112054070

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM01507
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM01507


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
1. Make up air shall be approximately the same as exhaust air for the kitchen. Your exhausting 9350 cfm and bringing in through the MAU 7324 cfm your lacking 2026 cfm’s (IMC2018,508.1) (If your bringing in the remaining cfm through the RTU’s, then in the RTU’s schedule you need to note that and that it will be interlocked to the kitchen and dishwasher hoods just like the makeup air unit is) RESPONSE: The additional makeup air required is being provided by the rooftop air conditioning units. A note to interlock the rooftop air conditioning units with the kitchen hoods exhaust fans has been added to the rooftop air conditioning unit schedule. See packaged air conditioning unit with gas heat schedule keynote 12, sheet M103. Complied
2. All equipment shall be on mechanical schedule and that includes coolers (IMC2018,106.3.1) RESPONSE: The walk-in cooler is a food service item specified and detailed in the food service plans. A note has been added in the mechanical plans that refers to the food service plans for information regarding the walk-in cooler. See sheet M200, keynote 34. See food service plans for walk-in cooler specifications and details. Complied
3. Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E500 ELECTRICAL ONE-LINE DIAGRAM: Fault currents misidentified. F2 is probably shown as F3, F4 isn’t calculated. Provided Calculations prove panels do have sufficient KAIC rating, this is an FYI to correct.


PLUMBING REVIEW COMMENTS:
Denied
Third Plumbing Review- Correct Plans not sent previous review
1). Same- Add Fixture center to side wall measurements to plan pages A300 & A301 -IPC 405.3.1
2 thru 7 OK
8). The selected dishwasher drain water connection backflow device chosen on plan page P300 is for low hazard applications only per table IPC 608.1, this is a high hazard application, the dishwasher discharge could contain chemicals & food waste
9). OK
10). OK
11). Employee Restroom on floor plan A120 & all plumbing pages can not open in to kitchen/food service area. -IPC 403.3.2 ( suggest have the restroom door open in to a vestibule, then vestibule door open to food service area) Update all affected pages


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov