Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T22CM01477
Parcel: 137055850

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM01477
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2022 KROBLES1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Completed
10/06/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM01449, T22CM01450, T22CM01451, T22CM01452, T22CM01453, T22CM01454, T22CM01455, T22CM01459, T22CM01477, T22CM01478, T22CM01479

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
All violations complied
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Conditionally Approved
Fourth Plumbing Review: OK Subject To Field Inspections
1). OK
2), OK
3 THRU 10 OK
11). OK
12 THRU 17 ok
18).OK- BBQ grills below trellis on landscape page 18 need an exhaust hood above. -IFGC 623.5 **Subject To Field Insp.**
"CJD ENGINEERING RESPONSE: Omit trellis above these BBQ. No overhead construction will be provided"
**Provide plan page where change is reflected**
18(B) OK- BBQ grill manual also require Grill enclosure to have ventilation-IFGC 305.1 **NO Response****Subject To Field Insp.**
19)OK
20). OK- note 85 on SU100 pool equipment capped for future for separate permit
21). OK- Field Verify Underground CSST per install instructions
22). OK
23). OK
24) OK
25). OK- SUBJECT TO FIELD VERIFY FIRE PIT GAS FEATURE INSTALL REQUIREMENTS & REQUIRE ENCLOSURE
VENTING PER INSTALL INSTUCTIONS


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov