Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM01443
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/21/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T22CM01443 916 W Cushing St – PAD-10 New SFR (1st Review) TRANSMITTAL DATE: March 15, 2022 This site is located in PAD-10, a single-family residence is an allowed use in the PAD. 1. Per page 42 of the PAD design review is required. Provide design review approved plans with your next submittal. 2. Provide the approve Pima Country Combo Request from with your next submittal. Also remove the property line shown between lot 73 & 74 from the plan. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
| 03/21/2022 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 03/21/2022 | SSHIELD1 | NPPO | REVIEW | Passed | |
| 03/21/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T22CM01443 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL COMMENTS : 1. Provide a legible profession seal on the plans. 2. Show compliance with the Inclusive Home Design Ordinance adopted by the City of Tucson Ordinance #10463 on 10/16/2007. Notate accessible route, minimum door width, changes in floor elevation, door hardware, electrical outlet reach range, grab bar reinforcement, etc. 3. Show compliance with the Electric Vehicle Supply Equipment Ordinance adopted by the City of Tucson Ordinance #11844 on 6/22/2021. Include a 40 ampere 240 volt dedicated branch circuit with a NEMA 14-50R receptacle for charging an electric vehicle at a proposed parking space. SITE PLAN: 1. Show all utility lines from meter to building, R106.1.1. . PLANS: 1. Show compliance with R310 providing egress from bedrooms with minimum net clear opening area of 5.7 SQ FT (5 SQ FT 1st floor). Also, show the minimum net clear opening dimension of 24” height and 20” width, and maximum sill height of 44”. SECTIONS - DETAILS: 1. Show air-permeable insulation directly under the air-impermeable insulation without air gaps, R806.5.5.1.3. Update sheets with keynote 7.03 and 7.04 showing separation. ELECTRICAL PLANS: 1. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3. Remove circuit #25 from both kitchen and pantry and garage. Also, add a second countertop circuit. 2. Garage Receptacle Location: a 20 AMP receptacle outlet is required at each vehicle bay not more than 5.5 feet above the floor, E3901.9. 3. Provide the Electric Vehicle Supply Equipment 40 ampere 240 volt dedicated branch circuit with a NEMA 14-50R receptacle and label the circuit “EV Ready” and locate the receptacle at a parking area, N1104.2.1. Include the Electric Vehicle load entry (typically 7680 watts) in the electrical load calculations (continuous demand) like the HVAC entry, N1104.2.2. INTERNATIONAL ENERGY CONSERVATION CODE: 1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans. Please contact the plans reviewer if you have any questions: Ken Van Karsen (520) 837-4912 PDSD-Residential@tucsonaz.gov City of Tucson Residential Plan Review |
| 04/05/2022 | JPEELDA1 | FIRE | REVIEW | Approved |