Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2022 ARUIZ1 OIP REVIEW Reqs Change FROM: Name
PDSD Residential Review Section

PROJECT: T22CM01439
Roof top Solar Panels (1st Review)

TRANSMITTAL DATE:April 20 , 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.

COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments
COMMENT: Show the sum of the main and backfeed breakers not exceeding 120% of the busbar (and conductor) rating, NEC 690.64 & 705.12 (D). Show the backfeed breaker incompliance with the bus limitation or increase the service panel rating

COMMENT: Residential will review the application on the next submittal

If you have any questions about this transmittal, Contact Angie.Ruiz@Tucsonaz.gov any time during the week by email

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans

Final Status

Task End Date Reviewer's Name Type of Review Description
05/31/2022 NGARCIA3 OUT TO CUSTOMER Completed