Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM01439
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/20/2022 | ARUIZ1 | OIP | REVIEW | Reqs Change | FROM: Name PDSD Residential Review Section PROJECT: T22CM01439 Roof top Solar Panels (1st Review) TRANSMITTAL DATE:April 20 , 2022 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed. COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments COMMENT: Show the sum of the main and backfeed breakers not exceeding 120% of the busbar (and conductor) rating, NEC 690.64 & 705.12 (D). Show the backfeed breaker incompliance with the bus limitation or increase the service panel rating COMMENT: Residential will review the application on the next submittal If you have any questions about this transmittal, Contact Angie.Ruiz@Tucsonaz.gov any time during the week by email RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/31/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |