Review Date Reviewer's Name Type of Review Description Status Comments
03/21/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1: Per the IBC Section 107, permit submittal documents shall be prepared by a registered design professional. Please provide.
2. Sheet A1; Floor Plan: The direction of swing of the new security door shall meet the requirements of the IBC Section 1010.1.2.1. Please verify and indicate on the drawings the requirements are met.
3. Sheet A1; Floor Plan: The new security door operations must meet the requirements of the IBC Section 1010.1.9. Please verify and indicate on the drawings the requirements are met.
4. General: Please provide a site plan per the IBC Section 107.2.6, indicating the location of the building on the site, and the location of the area of the building where the work shall be done.
5. General: Please provide a code analysis on the drawings for this project. Include the Occupancy Classification, Occupant Load, Construction Type, Building SF, and applicable Building Codes.
6. General: Please provide written responses to all review comments.