Permit Number: T22CM01386
Parcel: 141090320

Address:
8000 S KOLB RD

Review Status: Active

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM01386
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2022 JVINCEN1 FIRE REVIEW Approved
03/16/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Please provide dimensioned drawings that indicate the structural framing layout and location, including framing sizes, foundation sizes, etc. In addition, provide structural elevations, sections, and details as required. City of Tucson inspectors are not asked to interpret the construction of the structure from the information in the structural calculations.
2. General: Please provide on a drawing the material strengths, design loads, etc., for this project. In addition, provide a project narrative.
3. General: Please provide a Special Inspections Certificate with Parts A and B completed as required. This form may be found at www.tucsonaz.gov/PDSD.
4. General: Please provide written responses to all review comments.
03/22/2022 SSHIELD1 ENGINEERING REVIEW Denied See Zoning comments
03/22/2022 STEVE SHIELDS ZONING REVIEW Denied The address on the application is not correct. Based on the addressed on the plans this should be for 8401 S Kolb Rd. 8000 S Kolb is an Industrial site. 8401 S Kolb Rd is not within the City of Tucson’s jurisdiction.