| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/09/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 03/23/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. Is electrical service (SES 2) new or an upgrade? Where is 'SES 1' ? Show location of 'SES 1' and provide Permanent Plaque at each service location per NEC 230.2E Also provide for a common Grounding Electrode per NEC 250.58, if applicable. 2.Verify that there is a 120 volt receptacle within 25 feet of the mechanical equipment for maintenance as required per NEC art 210.63 3. Verify that there is a main circuit breaker for the new panel ‘LGN1’, the panel schedule states both? If not, provide overcurrent protection for the 30 KVA transformer secondary feeders and new Panel ‘LGN1’. NEC 240.4, 408.36B. 4. Provide a grounding detail for ‘SES 2’ and the 30 KVA transformer. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |