Permit Number: T22CM01362
Parcel: 12606204A

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM01362
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/23/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Is electrical service (SES 2) new or an upgrade? Where is 'SES 1' ? Show location of 'SES 1' and provide Permanent Plaque at each service location per NEC 230.2E Also provide for a common Grounding Electrode per NEC 250.58, if applicable.

2.Verify that there is a 120 volt receptacle within 25 feet of the mechanical equipment for maintenance as required per NEC art 210.63

3. Verify that there is a main circuit breaker for the new panel ‘LGN1’, the panel schedule states both? If not, provide overcurrent protection for the 30 KVA transformer secondary feeders and new Panel ‘LGN1’. NEC 240.4, 408.36B.

4. Provide a grounding detail for ‘SES 2’ and the 30 KVA transformer.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/24/2022 NGARCIA3 OUT TO CUSTOMER Completed