Permit Number: T22CM01343
Parcel: 107130960

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM01343
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Show the complete specifications for each heat pump system, including the SEER for each system. Reference: Sections R103.2, R403.7 and R501.5, IECC 2018.]
2. Comment not addressed. [Initial comment: Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections R302.2 and R403.7, IECC 2018 as amended by the City of Tucson.]
3. Comment not addressed. [Initial comment: Provide mechanical ventilation for each dwelling unit. Reference: Section R403.6 and R503.1.2, IECC 2018.]
4. Comment not addressed. [Initial comment: Provide guards for equipment located within 10 feet of a roof edge or of a walking surface that is elevated more than 30 inches above the adjoining grade. Reference: Section 304.11, IMC 2018.]
08/09/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved