Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM01343
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/11/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. Provide complete panel schedules for all panels. 2. Branch circuits being modified shall comply with NEC art 210.12D. 3. Load centers shall not be located in closets or bathrooms NEC 240.24(D)(E). 4. Verify that a 120 volt receptacle is provided for Mechanical Equipment maintenance per NEC 210.63. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 05/12/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Show the complete specifications for each heat pump system, including the SEER for each system. Reference: Sections R103.2, R403.7 and R501.5, IECC 2018. 2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections R302.2 and R403.7, IECC 2018 as amended by the City of Tucson. 3. Provide mechanical ventilation for each dwelling unit. Reference: Section R403.6 and R503.1.2, IECC 2018. 4. Provide guards for equipment located within 10 feet of a roof edge or of a walking surface that is elevated more than 30 inches above the adjoining grade. Reference: Section 304.11, IMC 2018. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/12/2022 | VVERA1 | OUT TO CUSTOMER | Completed |