Permit Number: T22CM01292
Parcel: 140211790

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM01292
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2022 SBLOOD1 ENGINEERING REVIEW Passed
03/08/2022 IMONSHI1 ZONING REVIEW Reqs Change FROM: Iman Monshizadeh

PDSD Zoning Review Section

PROJECT: T22CM01292 – Room Addition

Plot Plan Review (1st Review)

1610 E Holladay / R-1 Zone

TRANSMITTAL DATE: 03/08/2022



Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.



1.COMMENT: In an R-1 Zone, a floor plan of the existing residence is required to verify bedroom count as per 4.9.7.B.7 of the UDC. Provide a floor plan for the existing residence on the next submittal.

https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-2638



2.COMMENT: Provide setback dimensions for the existing shed from the south and east property line. Provide the height of the shed on the next submittal.

3.COMMENT: Provide wall heights for the new flex room on the elevations page. Wall height is measure from design grade to top of wall.



For questions regarding Zoning comments, please contact me at: Iman.Monshizadeh@tucsonaz.gov

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp
03/08/2022 IMONSHI1 NPPO REVIEW Passed
03/18/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM01292

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. 2018 IRC Section R106.1.1. Revise site plan drawing with locations, sizes, and meters of building utility lines for gas, water, electric and sewer or septic lines from property line to building.
2. 2018 IRC Section R305.1. Revise drawings with 7 feet minimum ceiling height.
3. 2018 IRC Added Table N1101.9.1. Provide specification information on 5 1/2" Batt ceiling insulation with R-Value 38 (U-factor 0.030) or revise drawings with 2 x 12 rafters for 12" Batt listed on sheet 2.


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Approved

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov