Permit Number: T22CM01285
Parcel: Unknown

Address:
5834 E 22ND ST

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM01285
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a complete diagram of the natural gas distribution system showing all the loads and developed lengths of the distribution piping. Reference: Section 402.2, IFGC 2018.
2. Revise the configuration of the natural gas sediment traps, as shown on the sketch, to comply with the requirements of Section 408.4, IFGC 2018.
3. Show the appliance shutoff valves on the sketch. The sediment trap is to be located downstream of the appliance shutoff valve, as close to the appliance as possible.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/23/2022 VVERA1 OUT TO CUSTOMER Completed