Permit Number - T22CM01285
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/23/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a complete diagram of the natural gas distribution system showing all the loads and developed lengths of the distribution piping. Reference: Section 402.2, IFGC 2018. 2. Revise the configuration of the natural gas sediment traps, as shown on the sketch, to comply with the requirements of Section 408.4, IFGC 2018. 3. Show the appliance shutoff valves on the sketch. The sediment trap is to be located downstream of the appliance shutoff valve, as close to the appliance as possible. |