Permit Number: T22CM01257
Parcel: 113021080

Address:
1230 E ALLEN RD

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM01257
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2022 SBLOOD1 ENGINEERING REVIEW Passed
03/09/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review


PROJECT:
T22CM01257
1230 E Allen Rd – R-2
Raise roof pitch and replace shingles (1st Review)

TRANSMITTAL: March 9, 2022
This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

1. As raising the roof pitch could affect perimeter yard setbacks provide 4 sided fully dimensioned elevations and a residential plot plan that meets the requirements found at: Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf.

2. Permit T21CM06318 will either need to be approved prior approval of this permit or withdrawn.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
03/09/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

Provide a Framing Plan showing the rafter, joist or truss layout with span dimensions, R804 or provide an engineer’s calculation, design and seal for a performance design when minimum sizes are not code compliant with the IRC, R301.1

Show compliance with R802.3.1 with continuous ceiling joist and collar ties in the upper third of attic space.

Provide a Section Detail showing rafter (truss) to wall connections with (H2.5) ties having a resistance to uplift of not less than 365 pounds, R802.11.1.

Show the placement and rating of ceiling/roof insulation for determining the need for attic ventilation, R806.

Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c ceiling framing, IRC table R702.3.5 footnote d.

Show roof sheathing size and fastening, Table R602.3(1).
03/09/2022 SSHIELD1 NPPO REVIEW Passed