Permit Number: T22CM01217
Parcel: 131010570

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM01217
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Please provide a site plan that indicates all areas of all buildings that require fire damage repair.
2. General: Please provide a narrative on the site plan indicating the areas to be repaired, and specific items to be repaired or replaced.
3. General: Please provide details as required for the construction of the repaired or replaced items.
4. General: Please provide written responses to all review comments.
03/07/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The notice of violation indicates that the gas and water distribution piping is to be replaced. Provide a schematic for the replacement gas piping system showing the gas loads, developed pipe lengths, pipe sizes, and the pipe material. Show pipe material and sizes of the water piping being replaced. Reference: Section 107.2.1, IBC 2018.
03/16/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. The building comments asked for plans with detailed information as to the full scope of work being done. Please include electrical.

Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements

Final Status

Task End Date Reviewer's Name Type of Review Description
03/16/2022 NGARCIA3 OUT TO CUSTOMER Completed