Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM01194
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/24/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet 1; Code: Revise the Code to the 2018 IBC with local amendments. 2. Sheet 2; Floor Plan: A 4' x4' window is indicated on the plan. Indicate on this sheet the window meets the criteria of the IBC Section 1030 (operational constraints, minimum size, minimum dimensions, maximum height from floor). 3. General: Care facilities fall under the requirements of the IBC. 4. General: Per the IBC Section 420.4, all Group R occupancies shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.2.8. Please provide. 5. General: Please provide written responses to all review comments. |
| 06/13/2022 | JPEELDA1 | FIRE | REVIEW | Approved |