Permit Number - T22CM01180
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/08/2022 | KROBLES1 | OIP | REVIEW | Reqs Change | FROM: Krystal Robles PDSD Residential Review Section PROJECT: (Project)T22CM01180 Roof top Solar Panels (1st Review) (Address) TRANSMITTAL DATE: 4/8/2022 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed. COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments. COMMENT: Show the sum of the main and backfeed breakers not exceeding 120% of the busbar (and conductor) rating, NEC 690.64 & 705.12 (D). Show the backfeed breaker incompliance with the bus limitation or increase the service panel rating. Comment: Provide a 125amp main or a 225amp buss panel. |