Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM01167
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/24/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Secure the refrigerant circuit access ports of the condensing units to prevent unauthorized access. Reference: Section 1101.10, IMC 2018. |
| 02/24/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the gas diagram on sheet P2.0 to show the size of the gas main between AHU-9 and AHU-10. Reference: Section 402.2, IFGC 2018. |
| 03/15/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. Verify there are adeqate maintenance receptacles throughout the building to provide for HVAC equipment maintenance power. NEC 210.63 2. The printing in the electrical plans at the bottom of the plan sheets and OCPD rating in the panel schedules is not legible. Please correct the issue and resubmit the plans. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/15/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |